Mining Cables - HELUPOWER® H07RN-F LS0H
Exhibitor
HELU KABEL GmbH
Technical Data
Rubber connection cable acc. to DIN VDE 0285-525-2-21 / DIN EN 50525-2-21Temperature rangeflexible -40°C to +90°C
fixed -50°C to +90°CPermissible operating temperature of the conductor+90°CShort circuit temperature at the conductor+250°CNominal voltageAC U0/U 450/750 VMax. permissible operating voltagealternating current (AC) conductor/earth 476 V
three-phase alternating current (AC) conductor/conductor 825 V
direct current (DC) conductor/earth 619 V
direct current (DC) conductor/conductor 1238 VTest voltage core/core2500 VMinimum bending radiusflexible 6x Outer-Ø
fixed 4x Outer-Ø
Details
Cable Structure
Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
Core insulation: Special rubber
Core identification acc. to DIN VDE 0293-308,
1 core(s): black
2 - 5 core(s): colour coded
7 - 12 core(s): black cores with consecutive labeling in white digits
Protective conductor: starting with 3 cores,
G = with protective conductor GN-YE, in the outer layer,
x = without protective conductor
Cores stranded in layers with optimal lay lengths
Outer sheath: Special rubber
Sheath colour: black
Properties
resistant to: oil, UV radiation, ozone, weathering effects, lubricating oils, greases
for outdoor use
halogen-free
Tests
halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
corrosiveness of combustion gases acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2
oil-resistant acc. to DIN VDE 0473-811-404 / DIN EN 60811-404 / IEC 60811-404
ozone-resistant acc. to DIN VDE 0473-811-403 / DIN EN 60811-403
certifications and approvals:
HAR
EAC
Notes
the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
Halogen-free rubber sheathed cables for use with medium mechanical stress in dry, damp, wet rooms and outdoors. Can only be used in stagnant waters (also in salt water) up to a water depth of 100 m (AD8) and a water temperature of min. +5°C. When installed in pipes or similar closed systems, the use of the cable is permitted up to and including 1000 V AC voltage or up to 750 V DC voltage against earth.